Quick answer: A 3-ton AC moves about 1,200 CFM, which needs a 16-inch round supply trunk and a 18-inch return at 0.08 in. w.c. per 100 ft. A 6-inch round duct carries about 97 CFM, an 8-inch about 207 CFM and a 10-inch about 372 CFM at the same friction rate. Return ducts run a size larger because return air should move more slowly.
Duct CFM chart (round duct)
How much air each round metal duct carries at three common friction rates, and the most it should carry once the velocity limit is applied.
| Round duct | CFM at 0.06 | CFM at 0.08 | CFM at 0.10 | Max supply CFM* | Max return CFM* |
|---|---|---|---|---|---|
| 4 in | 28 | 33 | 37 | 33 | 33 |
| 5 in | 51 | 60 | 67 | 60 | 60 |
| 6 in | 83 | 97 | 109 | 97 | 97 |
| 7 in | 125 | 145 | 163 | 145 | 145 |
| 8 in | 178 | 207 | 232 | 207 | 207 |
| 9 in | 242 | 282 | 317 | 282 | 282 |
| 10 in | 320 | 372 | 419 | 372 | 372 |
| 12 in | 518 | 603 | 678 | 603 | 550 |
| 14 in | 779 | 906 | 1,019 | 906 | 748 |
| 16 in | 1,108 | 1,290 | 1,450 | 1,257 | 977 |
| 18 in | 1,513 | 1,760 | 1,980 | 1,590 | 1,237 |
| 20 in | 1,999 | 2,325 | 2,615 | 1,963 | 1,527 |
| 22 in | 2,571 | 2,991 | 3,364 | 2,376 | 1,848 |
| 24 in | 3,235 | 3,764 | 4,233 | 2,827 | 2,199 |
Friction rates in inches of water column per 100 ft. *At 0.08 in. w.c./100 ft and no faster than 900 fpm (supply) or 700 fpm (return).
Duct sizing chart by AC size
Main trunk sizes for a whole system at 400 CFM per ton and 0.08 in. w.c. per 100 ft.
| AC size | Airflow | Supply trunk (round) | Supply trunk (rectangular) | Return (round) |
|---|---|---|---|---|
| 1.5 ton | 600 CFM | 12 in | 8 × 16 in | 14 in |
| 2 ton | 800 CFM | 14 in | 8 × 20 in | 16 in |
| 2.5 ton | 1,000 CFM | 16 in | 8 × 24 in | 18 in |
| 3 ton | 1,200 CFM | 16 in | 8 × 28 in | 18 in |
| 3.5 ton | 1,400 CFM | 18 in | 8 × 32 in | 20 in |
| 4 ton | 1,600 CFM | 20 in | 10 × 28 in | 22 in |
| 5 ton | 2,000 CFM | 22 in | 10 × 34 in | 24 in |
Many homes split the airflow between two trunks, or run a rectangular trunk off the air handler. For the size of the equipment itself, use the AC size calculator or see AC tonnage by square footage.
Rectangular to round duct chart
Common rectangular sizes, the round duct each one matches, and its airflow at 0.08 in. w.c. per 100 ft.
| Rectangular duct | Equivalent round | CFM at 0.08 |
|---|---|---|
| 6 × 8 in | 7.6 in | 178 |
| 6 × 10 in | 8.4 in | 235 |
| 6 × 12 in | 9.1 in | 294 |
| 8 × 8 in | 8.7 in | 261 |
| 8 × 10 in | 9.8 in | 350 |
| 8 × 12 in | 10.7 in | 441 |
| 8 × 14 in | 11.5 in | 534 |
| 8 × 16 in | 12.2 in | 628 |
| 10 × 10 in | 10.9 in | 471 |
| 10 × 12 in | 12.0 in | 598 |
| 10 × 14 in | 12.9 in | 728 |
| 10 × 16 in | 13.7 in | 861 |
| 10 × 20 in | 15.2 in | 1,133 |
| 12 × 12 in | 13.1 in | 763 |
| 12 × 16 in | 15.1 in | 1,108 |
| 12 × 20 in | 16.8 in | 1,467 |
| 12 × 24 in | 18.3 in | 1,834 |
| 14 × 20 in | 18.2 in | 1,818 |
How many CFM per ton?
| Climate | CFM per ton | Why |
|---|---|---|
| Humid (Southeast, Gulf Coast) | 350 | Slower air over the coil removes more moisture |
| Typical | 400 | The standard design figure |
| Dry (Southwest, mountain West) | 450 | Faster air gives more sensible cooling |
These are starting points. The equipment's own fan tables, and a contractor's Manual S selection, set the final airflow.
How the calculator sizes a duct
- Airflow
It starts from the CFM you enter, or from tons × CFM per ton. For a room, it uses the room's share of the system airflow: room BTU ÷ 12,000 × CFM per ton.
- Friction
It finds the smallest standard round duct whose friction loss stays at or below your chosen rate, using the standard friction equation for galvanized round duct: friction = 0.109136 × CFM1.9 ÷ diameter5.02.
- Velocity
It checks the air speed against Manual D's maximums, 900 fpm for supply and 700 fpm for return, and steps up a size if needed.
- Rectangular options
It lists rectangular ducts 6 to 12 inches tall that perform at least as well, using the Huebscher equivalent-diameter formula, at aspect ratios up to 4 to 1.
Flex duct vs metal duct
Flex duct that is pulled tight, with no sag or compression, performs close to metal duct of the same diameter. Installed loosely, it is a different story: as little as 4% compression can mean a 12-inch flex duct is needed where a 10-inch duct would otherwise do. If your flex runs are long or can't be stretched straight, size up one step.
What this calculator doesn't do
It sizes one duct section at a time from a friction rate you choose. A full ACCA Manual D design also adds the equivalent length of every elbow and fitting, checks the blower's available static pressure, and balances each run. Use these results to sanity-check a design or a contractor's drawing, not as a replacement for Manual D. Room loads come first: see Manual J load calculation for a room-by-room estimate.